FOUR SELECTABLE D.C. RANGES
200 A, 2 mA, 20 mA, 200 mA
MINIMUM AND MAXIMUM DISPLAY CAPTURE
LCD, REFLECTIVE OR RED/GREEN LED BACKLIGHTING
0.48" (12.2 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARD
OPTIONAL SERIAL COMMUNICATIONS CARD (RS232 or RS485)
OPTIONAL USB PROGRAMMING CARD
OPERATES FROM 9 TO 28 VDC POWER SOURCE
FRONT PANEL OR CRIMSON PROGRAMMABLE
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
MODEL CUB5I - MINIATURE ELECTRONIC 5-DIGIT DC CURRENT METER
GENERAL DESCRIPTION
The CUB5 provides the user the ultimate in flexibility, from its complete user
programming to the optional setpoint control and communication capability.
The CUB5I accepts a DC Current input signal and provides a display in the
desired unit of measure. The meter also features minimum and maximum
display capture, display offset, units indicator, and programmable user input.
The display can be toggled either manually or automatically between the
selected displays.
The CUB5 display has 0.48" (12.2 mm) high digits. The LCD is available in
two versions, reflective and red/green backlight. The backlight version is user
selectable for the desired color and also has variable display intensity.
The capability of the CUB5 can be easily expanded with the addition of
option cards. Setpoint capability is field installable with the addition of the
setpoint output cards. Serial communications capability for RS232 or RS485 is
added with a serial option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the
unit and sensors.
CURRENT
The CUB5I is the DC Current meter. It features 4 current input ranges, that
are selected by the user via a programming jumper and software input range
selection. The ranges consist of following: 200 A, 2 mA, 20 mA, or 200 mA.
Users should select the appropriate current range that covers their maximum
signal input.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
Bulletin No. CUB5I-K
Drawing No. LP0658
Released 02/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
.13 (3.3)
(43.4)
1.71
2.95 (74.9)
SEL
.15 (3.8)
1.54 (39.1)
RST
(68 )
+.025
-.000
+8
-0
1.29 (32.8)
2.68
-.000
1.30
(33 )
-0
+6
+.024
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
C
C
US LISTED
US LISTED
U
L
R
51EB
IND. CONT. EQ.
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - DIMENSIONS In inches (mm)

1 FOUR SELECTABLE D.C. RANGES 200 A, 2 mA, 20 mA, 200 mA MINIMUM AND MAXIMUM DISPLAY CAPTURE LCD, REFLECTIVE OR RED/GREEN LED BACKLIGHTING 0.

Seite 2 - ORDERING INFORMATION

Enter the reset action of the output. See figure for details.Auto = Automatic action; This action allows the output to automatically reset off at the

Seite 3 - 2.0 SETTING THE JUMPERS

116.5 MODULE 5 - SERIAL SETUP PARAMETERS (5-SEr)LIMITED WARRANTYThe Company warrants the products it manufactures against defects in materials and wo

Seite 4 - 3.0 INSTALLING PLUG-IN CARDS

Setpoint ActionSetpoint SelectSetpoint ValueOutput Reset ActionHysteresis ValueOff Time DelayOn Time DelayOutput Reset W/Display ResetChange Display

Seite 5 - 4.6 USB PROGRAMMING

1. DISPLAY: 5 digit LCD 0.48" (12.2 mm) high digitsCUB5IR00: Reflective LCD with full viewing angleCUB5IB00: Transmissive LCD with selectable red

Seite 6 - 6.0 PROGRAMMING THE METER

3ADDING OPTION CARDSThe CUB5 meters can be fitted with optional output cards and/or serial communications cards. The details for the plug-in cards can

Seite 7

WIRING OVERVIEWElectrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’

Seite 8 - LO-En LO-t FCS

COMMINP +MODEL INPUT POWER:OUTPUT POWER:85-250 VAC, 50/60Hz, 14VAOPERATING TEMP: 0° TO 60°C12VDC UNREG. @ 400mA+12VDC COMMONM3424BTERMINALAC I

Seite 9 - ARAMETERS (3-dSP)

65.0 REVIEWING THE FRONT BUTTONS AND DISPLAYSEL RSTPROGRAMMING MODE ENTRY (SEL BUTTON)It is recommended all programming changes be made off line, or b

Seite 10 - Unit Only

Display DecimalPointFilter SettingFilter BandInput Value for Scaling Point 1Display Value For Scaling Point 1User Input AssignmentInput RangeSELrANGEd

Seite 11 - PAr Addr Abbr

Entering Code 66 will overwrite all user settings with the factory settings. The meter will display rESEt and then return to CodE 00. Press the SEL bu

Seite 12 - Press and hold SEL button to

9The Security Code determines the programming mode and the accessibility of programming parameters. This code can be used along with the Program Mode