13
ALARM 1 (40018) & 2 (40014) ACTION REGISTER TABLE
INPUT TYPE REGISTER (40008) TABLE
SENSOR FAILURE ACTION REGISTER (40022) TABLE
FOR ALARM STATE CONDITION
USER INPUT ACTION REGISTER (40013) TABLE
Examples:
Alarm 1 (40018):
Stand-by off, Latch on = 0 0 0 1 <1 >
Absolute Lo, Balanced = 0 0 1 0 < 2>
<1 2>
Alarm 2 (40014):
Stand-by on, Latch off = 0 0 1 0 <2 >
Band Outside = 0 1 1 1 < 7>
<27>
COMMUNICATIONS REGISTER (40026) AND COILS 1-8 TABLE
* When reading register 40026, B7 will be a 0. When writing (changing ITMS communications to the new setting), change B7 to a 1.
Mode Parity Baud
Coil 8
B7*
Coil 7
B6
Coil 6
B5
Coil 5
B4
Coil 4
B3
Coil 3
B2
Coil 2
B1
Coil 1
B0
Coil 8 =0
HEX
Coil 8 =1
HEX
RTU 8N1,2 300 0 / 1 0 1 0 0 0 0 0 <20> <A0>
RTU 8N1,2 600 0 / 1 0 1 0 0 0 0 1 <21> <A1>
RTU 8N1,2 1200 0 / 1 0 1 0 0 0 1 0 <22> <A2>
RTU 8N1,2 2400 0 / 1 0 1 0 0 0 1 1 <23> <A3>
RTU 8N1,2 4800 0 / 1 0 1 0 0 1 0 0 <24> <A4>
RTU 8N1,2 9600 0 / 1 0 1 0 0 1 0 1 <25> <A5>
RTU 8N1,2 19200 0 / 1 0 1 0 0 1 1 0 <26> <A6>
RTU 8N1,2 38400 0 / 1 0 1 0 0 1 1 1 <27> <A7>
RTU 8E1 300 0 / 1 0 1 0 1 0 0 0 <28> <A8>
RTU 8E1 600 0 / 1 0 1 0 1 0 0 1 <29> <A9>
RTU 8E1 1200 0 / 1 0 1 0 1 0 1 0 <2A> <AA>
RTU 8E1 2400 0 / 1 0 1 0 1 0 1 1 <2B> <AB>
RTU 8E1 4800 0 / 1 0 1 0 1 1 0 0 <2C> <AC>
RTU 8E1 9600 0 / 1 0 1 0 1 1 0 1 <2D> <AD>
RTU 8E1 19200 0 / 1 0 1 0 1 1 1 0 <2E> <AE>
RTU 8E1 38400 0 / 1 0 1 0 1 1 1 1 <2F> <AF>
RTU 8O1 300 0 / 1 0 1 1 1 0 0 0 <38> <B8>
RTU 8O1 600 0 / 1 0 1 1 1 0 0 1 <39> <B9>
RTU 8O1 1200 0 / 1 0 1 1 1 0 1 0 <3A> <BA>
RTU 8O1 2400 0 / 1 0 1 1 1 0 1 1 <3B> <BB>
RTU 8O1 4800 0 / 1 0 1 1 1 1 0 0 <3C> <BC>
RTU 8O1 9600 0 / 1 0 1 1 1 1 0 1 <3D> <BD>
RTU 8O1 19200 0 / 1 0 1 1 1 1 1 0 <3E> <BE>
RTU 8O1 38400 0 / 1 0 1 1 1 1 1 1 <3F> <BF>
Latched
Off=Auto
2nd Nibble
HEX
Stand By B7 B6 B5
off off 0 0 0 0 <0 >
off on 0 0 0 1 <1 >
on off 0 0 1 0 <2 >
on on 0 0 1 1 <3 >
B4
< 8>
< 7>
0
1
0
1
0
1
1
0
2
2
8
7
Band Inside
Band Outside
< 6>011026Deviation Lo
< 5>101025Deviation Hi
< 4>0010214Absolute Lo, unbalanced
< 3>1100213Absolute Hi, unbalanced
< 2>0100212Absolute Lo, balanced
< 1>1000211Absolute Hi, balanced
< 0>0000210Manual
1st Nibble
HEX
B0B1B2B3ALARMSMODEACTION
See Setpoint Alarm Figures, Page 5, for illustrations of alarm operation.
MODE TYPE MODE TYPE MODE TYPE
0 Tc - T 5 Tc - S 10 RTD - 385
1 Tc - E 6 Tc - B 11 RTD - 392
2 Tc - J 7 Tc - N 12 RTD - 672
3 Tc - K 8 Tc - C 13 LIN Ohms
4 Tc - R 9 LIN mV
MODE ACTION ALARM INPUT ACTIVATION
<0000> Reset 1 Level (Maintained)
<0001> Reset 2 Level (Maintained)
<0002> Reset 1 & 2 Level (Maintained)
<0003> Set 1 Level (Maintained)
<0004> Set 2 Level (Maintained)
<0005 Set 1 & 2 Level (Maintained)
<0010> Reset 1 Edge (Momentary)
<0011> Reset 2 Edge (Momentary)
<0012> Reset 1 & 2 Edge (Momentary)
<0013> Set 1 Edge (Momentary)
<0014> Set 2 Edge (Momentary)
<0015> Set 1 & 2 Edge (Momentary)
MODE ALARM 1 ALARM 2
0 Off Off
1 On On
2 Off On
3 On Off