Select  to perform either of the Factory Service Operations shown below.
FACTORY SERVICE OPERATIONS


Entering Code 50 will display the model and version (x.x) of the meter. The
display then returns to . Press the PAR key to exit the module.
VIEW MODEL AND VERSION DISPLAY


Entering Code 66 will overwrite all user settings with the factory default
settings. The meter will display  and then return to  . Press the
PAR key to exit the module.
RESTORE FACTORY DEFAULT SETTINGS


 
5.4 MODULE 4 - SETPOINT OUTPUT PARAMETERS ()
PAR



Setpoint
Standby
Operation

Setpoint Output
Power-up
State
 
Setpoint
Boundary
Type

Setpoint
Enable
Setpoint
Select
 
Setpoint
Assignment

SP2 Output
Off at SP1
Output

Setpoint
Output Logic

Counter
Auto Reset
SP1 Output
Off at SP2
Output
Setpoint
Output
Action
Setpoint
Output
Time-out
 
Setpoint
Value
Setpoint
Output Reset
with Manual
Reset

Setpoint
Annunciator

SP1 Only
SP2 Only


PARAMETER MENU
Some Setpoint parameters will not appear depending on the Setpoint Assignment and Setpoint
Output Action selected. The Setpoint Parameter Availability chart below illustrates this.
* BOUNDARY Setpoint Action not applicable for Counter B assignment.
Select the Setpoint Output to be programmed, starting with Setpoint 1. The
” in the following parameters reflects the chosen Setpoint number. After the
selected setpoint is completely programmed, the display returns to  .
Repeat steps for Setpoint 2 if both Setpoints are being used. Select  to exit the
Setpoint programming module.
SETPOINT SELECT





Select  to enable the chosen setpoint and access the setup parameters. If
is selected, the unit returns to  and the setpoint is disabled.
SETPOINT ENABLE
 


PARAMETER
Standby Operation (Low ActingOnly)
YesNoYesYesNoYesOutput Reset with Manual Reset

NoNoNoYesNoYesSP2 Output Off at SP1 (SP2 only)

NoNoNoYesNoYesSP1 Output Off at SP2 (SP1 only)

NoNoNoYesNoYesCounter Auto Reset

YesYesYesNoYesNo

YesYesYesNoYesNoSetpoint Boundary Type

YesNoNoYesNoNoSetpoint Output Power-up State

YesYesYesYesYesYesSetpoint Annunciator

YesYesYesYesYesYesSetpoint Output Logic

YesYesYesYesYesYesSetpoint Value

NoNoYesNoNoYesSetpoint Output Time-out Value

LATCH

BOUNDARY

TIMED OUT

LATCH

BOUNDARY

TIMED OUT

DESCRIPTION
RATE ASSIGNMENTCOUNTER ASSIGNMENT (A or B)*